nVent_Core_Component_CMYK_F2-656x730.png

Pentair Thermal Management Becomes nVent
- A New Opportunity to Spark Innovation

Your trusted brands RAYCHEM, TRACER, NUHEAT, PYROTENAX and TraceTek are now part of nVent Thermal Management.

The new company website is in development and will be launched in January 2019. Until then, we are happy to serve your information needs through our current website.

For more information on nVent:
Download press release
Visit nVent.com
(currently English only)

nVent RAYCHEM Series-resistance SC Heat Trace Cables

Overview

RAYCHEM SC and SC/H series-resistance technology provides pipe freeze protection and high-temperature maintenance for longline heating applications. The RAYCHEM SC/F series-resistance technology provides freeze protection for longline applications with low heat loss.

SC Cable Performance
This series-resistance type heating cable can withstand continuous exposure to temperatures up to 482°F (250°C). All SC heating cables can be used for continuous circuit lengths of 1,000 up to 12,000 feet, powered from a single source and are capable of supporting voltages up to 600Vac.

Additional Product Information:

  1. RAYCHEM SC and SC/H electric heat trace cables are approved for use in non-hazardous and hazardous locations.
  2. RAYCHEM SC and SC/H electric heat trace cables are configured for use in areas where corrosives may be present
  3. RAYCHEM SC and SC/H electric heat trace cables meet the requirements of the U.S. National Electrical Code and the Canadian Electrical Code.

Industries Served:
Chemical and Pharmaceutical
Food and Beverage
Marine
Mining
Oil and Gas
Power

Technical Specifications

  1. The heating cable shall be a series resistance constant wattage heater. It shall consist of one, two, or three copper conductors or copper alloy conductors insulated with fiber glass braid for SC and SC/H cable along with high temperature heavy-walled fluoropolymer.
  2. The heating cable shall have a tinned or nickel-plated copper braid to provide a ground path. The braid shall be protected from chemical attack and mechanical abuse by a fluoropolymer outer jacket.
  3. The heating cable shall be constant wattage RAYCHEM SC, with continuous exposure capability up to 400°F (204°C), RAYCHEM SC/H with continuous exposure capability up to 482 °F (250°C), or SC/F with continuous exposure capabilities up to 195°F (90°C) as manufactured by nVent Thermal Management.

For detailed product specifications, please refer to the product datasheet.

Warranty

Warranty Information

Warranty Extension Available

Connection and Protection